SALAM SEJAHTERA

SALAM SEJAHTERA,SELAMAT DATANG KE HAMDISAAD74.BLOGSPOT

Friday 22 March 2013

Regulation 45. Corrosive service conditions.



                                     P.U.(A) 5/70
FACTORIES AND MACHINERY (STEAM BOILER AND
                    UNFIRED PRESSURE VESSEL)
                              REGULATIONS, 1970
            PART III - UNFIRED PRESSURE VESSELS

Regulation 45. Corrosive service conditions.

Where an unfired pressure vessel is to be subject to corrosive, abrasive or erosive conditions-
(i) the Chief Inspector may require that the scantlings of such vessel shall be increased
by an amount which he may deem appropriate before assigning and authorised safe
working pressure;

(ii) the Chief Inspector may require that a suitable lining shall be fitted to any part of such
vessel as he may specify before it is placed in service; and
 
(iii) an Inspector may require tell-tale holes to be drilled in the walls of such unfired
pressure vessel. Such holes shall be drilled to a depth not less than half the calculated
wall thickness less any corrosion allowance and shall be spaced not more than two feet
apart.



Copyright © 2004 PNMB-LawNet. All rights reserved.


No comments:

Post a Comment

Saya amat berterima kasih sekiranya anda dapat memberi komen yang baik tentang blog ini.

Note: only a member of this blog may post a comment.