SALAM SEJAHTERA

SALAM SEJAHTERA,SELAMAT DATANG KE HAMDISAAD74.BLOGSPOT

Friday 22 March 2013

Regulation 57. Stop valves.



P.U.(A) 5/70
FACTORIES AND MACHINERY (STEAM BOILER AND
                   UNFIRED PRESSURE VESSEL)
                             REGULATIONS, 1970
            PART III - UNFIRED PRESSURE VESSELS

Regulation 57. Stop valves.
(1) Every stop valve for a steam receiver shall comply with the provisions of these regulations
relating to main stop valves for steam boilers.

(2) A stop valve or cock shall not be fitted between any unfired pressure vessel shall and its
safety valve or rupture disc.

(3) A stop valve or cock shall not be fitted between any safety valve or rupture disc and its
discharge pipe.

(4) Where a stop valve is placed in the discharge line between a compressor and an air receiver,
a relief valve shall be placed between the compressor and the stop valve unless the compressor
is provided with an automatic unloading device.



Copyright © 2004 PNMB-LawNet. All rights reserved.


No comments:

Post a Comment

Saya amat berterima kasih sekiranya anda dapat memberi komen yang baik tentang blog ini.

Note: only a member of this blog may post a comment.