P.U.(A)
5/70
FACTORIES
AND MACHINERY (STEAM BOILER AND 
                    UNFIRED PRESSURE VESSEL)
                             REGULATIONS, 1970 
                        PART II - STEAM BOILERS
Regulation
15. Blow-down valves and cocks. 
(1) Every blow-down valve
or cock fitted to a steam boiler shall- 
(i) have a bore not less
than one inch in diameter; and
(ii) be fitted with a
device which shall indicate clearly the open and close positions. 
(2) Every blow-down cock
shall be of the bolted cover or double gland type.
(3) Every blow-down valve
or cock fitted to a shell-type steam boiler shall be attached direct to
the steam boiler shell as
near as practicable to the lowest part thereof;
Provided that in the case
of a horizontal cylindrical steam boiler it may be attached to a cast steel
tapered elbow of
substantial construction and adequate cross-section.
(4) Where the blow-down
pipes of two or more steam boilers are led into a common main, an
isolating valve of the
screw down non-return type shall be fitted between the blow-down valve or
cock on every steam boiler
and the common main. In such case only one operating key shall be
provided for the blow-down
valve or cocks.