P.U.(A)
5/70 
FACTORIES
AND MACHINERY (STEAM BOILER AND 
                   UNFIRED PRESSURE VESSEL)
                             REGULATIONS, 1970 
            PART III - UNFIRED PRESSURE VESSELS
Regulation
57. Stop valves. 
(1) Every stop valve for a
steam receiver shall comply with the provisions of these regulations
relating to main stop
valves for steam boilers. 
(2) A stop valve or cock
shall not be fitted between any unfired pressure vessel shall and its
safety valve or rupture
disc. 
(3) A stop valve or cock
shall not be fitted between any safety valve or rupture disc and its 
discharge pipe. 
(4) Where a stop valve is
placed in the discharge line between a compressor and an air receiver,
a relief valve shall be
placed between the compressor and the stop valve unless the compressor
is provided with an
automatic unloading device. 