P.U.(A)
5/70
FACTORIES
AND MACHINERY (STEAM BOILER AND
UNFIRED PRESSURE VESSEL)
REGULATIONS, 1970
PART II - STEAM BOILERS
Regulation
33. Boiler houses.
(1) Every steam boiler
house shall be of sufficient side to permit-
(i) the safe and efficient
working and maintenance of the steam boiler;
(ii) ample space between
the steam boiler and any other steam boiler, machinery, wall or
column, for inspection and
repairs (including the removal of any tubes):
Provided that in the case
of a vertical steam boiler there shall be a clear height not less
than three feet between
the top of the steam boiler and the roof and in the case of any
other type of steam boiler
there shall be a clear height not less than seven feet between
any platform or the top of
any setting and the roof, as the case may be.
(2) The floor of every
steam boiler house shall be kept at all times free of water and oil.
(3) Every part of any
steam boiler house in the vicinity of any oil burning equipment shall be
impervious to oil and so
graded as to prevent the accumulation of oil.
(4) Spaces at the top and
sides of any steam boiler shall not be used for storage purposes,
neither shall any
combustible material other than material used for firing any steam boiler be
stored or allowed to
accumulate near it.
(5) The door of any boiler
house shall not open inwards.