P.U.(A) 5/70
FACTORIES
AND MACHINERY (STEAM BOILER AND
UNFIRED PRESSURE VESSEL)
REGULATIONS, 1970
PART II - STEAM BOILERS
Regulation
35. Hand controlled burner system.
Every hand-controlled
burner system fitted to a steam boiler shall be provided-
(i) with a stop valve,
independent of the burner control valve, fitted as close to the burner
as practicable;
(ii) with means for
regulating the supply of air to the combustion chamber;
(iii) with means for
regulating by hand the supply of oil to the burner;
(iv) where an electric
motor is used to drive any oil pump, fan or compressor supplying oil
or air to the combustion
chamber, with:
(a) no-volt
protection on the starter of such motor; and
(b) a device
which automatically cuts off the supply of oil to the burner when the
electricity supply fails
and does not permit such supply to be resumed until the
device is re-set manually.